String Monitoring Station
Measurement technology cabinet for centrally recording and processing all system data in your PV power plant for indoor and outdoor.
Features
- Measurement of up to 32 strings
- DC circuit breaker
- Overvoltage protection
- Capability to connect analogue and digital signals
STRING MONITORING STATION V1
- Supply voltage: 10 … 60 V DC
- Current consumption: max. 58 mA at 24 V DC
- Operating temperature: - 20 … 35 °C (up to 40 °C for short periods)
- Enclosure: PES
- Components:
Positive terminal fuses
Circuit breaker
Optional Negative terminal fuses
Optional 1 x i’catcher - UV resistant: Yes
- Protection class: IP 54
- Dimensions (H x W x D): 750 x 750 x 300 mm
- Installation: Wall installation / plinth model
- String fuses: 15 A at 1,000 V DC, 30 kA
- Overvoltage protection Type I / II (Class B / C)
- Max. allowable
DC voltage: 1,000 V - DC circuit breaker Socomec 125 A / 160 A / 250 A
| Item Number | Select |
|---|---|
| 421.908 String Monitoring Station V1 8-0 |
|
| 421.909 String Monitoring Station V1 8-8 |
|
| 421.910 String Monitoring Station V1 16-0 |
|
| 421.911 String Monitoring Station V1 16-8 |
STRING MONITORING STATION V2
- Supply voltage: 10 … 60 V DC
- Current consumption: max. 116 mA at 24 V DC
- Operating temperature: - 20 … 35 °C (up to 40 °C for short periods)
- Enclosure: PES
- Components:
Positive terminal fuses
Circuit breaker
Optional Negative terminal fuses
Optional 2 x i’catcher - UV resistant: Yes
- Protection class: IP 54
- Dimensions (H x W x D): 750 x 1,000 x 300 mm
- Installation: Wall installation / plinth model
- String fuses: 15 A at 1,000 V DC, 30 kA
- Overvoltage protection Type I / II (Class B / C)
- Max. allowable
DC voltage: 1,000 V - DC circuit breaker Socomec 160 A / 250 A / 315 A
| Item Number | Select |
|---|---|
| 421.912 String Monitoring Station V2 16-0 |
|
| 421.913 String Monitoring Station V2 16-16 |
|
| 421.914 String Monitoring Station V2 32-0 |
|
| 421.915 String Monitoring Station V2 32-16 |