String Monitoring Station

Measurement technology cabinet for centrally recording and processing all system data in your PV power plant for indoor and outdoor.

Features

  • Measurement of up to 32 strings
  • DC circuit breaker
  • Overvoltage protection
  • Capability to connect analogue and digital signals

STRING MONITORING STATION V1

  • Supply voltage: 10 … 60 V DC
  • Current consumption: max. 58 mA at 24 V DC
  • Operating temperature: - 20 … 35 °C (up to 40 °C for short periods)
  • Enclosure: PES
  • Components:
    Positive terminal fuses
    Circuit breaker
    Optional Negative terminal fuses
    Optional 1 x i’catcher
  • UV resistant: Yes
  • Protection class: IP 54
  • Dimensions (H x W x D): 750 x 750 x 300 mm
  • Installation: Wall installation / plinth model
  • String fuses: 15 A at 1,000 V DC, 30 kA
  • Overvoltage protection Type I / II (Class B / C)
  • Max. allowable
    DC voltage: 1,000 V
  • DC circuit breaker Socomec 125 A / 160 A / 250 A
Item Number Select
421.908

String Monitoring Station V1 8-0

421.909

String Monitoring Station V1 8-8

421.910

String Monitoring Station V1 16-0

421.911

String Monitoring Station V1 16-8

STRING MONITORING STATION V2

  • Supply voltage: 10 … 60 V DC
  • Current consumption: max. 116 mA at 24 V DC
  • Operating temperature: - 20 … 35 °C (up to 40 °C for short periods)
  • Enclosure: PES
  • Components:
    Positive terminal fuses
    Circuit breaker
    Optional Negative terminal fuses
    Optional 2 x i’catcher
  • UV resistant: Yes
  • Protection class: IP 54
  • Dimensions (H x W x D): 750 x 1,000 x 300 mm
  • Installation: Wall installation / plinth model
  • String fuses: 15 A at 1,000 V DC, 30 kA
  • Overvoltage protection Type I / II (Class B / C)
  • Max. allowable
    DC voltage: 1,000 V
  • DC circuit breaker Socomec 160 A / 250 A / 315 A
Item Number Select
421.912

String Monitoring Station V2 16-0

421.913

String Monitoring Station V2 16-16

421.914

String Monitoring Station V2 32-0

421.915

String Monitoring Station V2 32-16